Measurement and control technology
A modular automation platform for energy and water facilities: acquisition, protection and control in plug-in modules, plus supervisory systems with a long track record in power plants. We supply modules, engineer systems and integrate them into existing control technology.

Modules
All modules share a common backplane bus, are hot-swappable and are parameterised by software. Analogue inputs are converted with at least 16 bits throughout.
- Protection, measurement and control in one family
- RS485, CAN and Ethernet on every communication module
- Modbus RTU, Modbus TCP, CANopen; IEC protocols on request
- Touch-panel HMI with built-in commissioning software

Intelligent universal module
Protection and control module for generators, transformers and lines: main and backup protection, acquisition of binary and analogue signals, switching outputs. With a fixed program it acts as a protection device, freely programmed as a PAC for your own sequences.
| Binary inputs | 32 |
|---|---|
| Binary outputs | 16 |
| Analogue inputs | 12, 16-bit, parallel, high speed |
| Variants | generator, transformer, line, capacitor and motor protection; synchronisation, speed, measurement, backup feed |
Measurement and control module
Acquisition of DC differential signals, standard signals and temperatures with limit monitoring: warning and fault on exceeding or falling below limits as switching output. High-precision variant with 0.05 % for Pt1000 sensors.
| Resolution | 16-bit |
|---|---|
| Variants | 24× temperature, 18× temperature, 12× temperature, 12× differential, 24× differential, 48× analogue |
| Accuracy (G series) | 0.05 %, Pt1000 |

Power supply and communication modules
Power supply module with integrated switch-mode supply for extension racks (e.g. 110 V or 220 V DC input), communication module as bridge between backplane and outside world, and communication module with redundant 24 V feed and automatic changeover.
| Interfaces | RS485, CAN, Ethernet 10/100 |
|---|---|
| Protocols | Modbus RTU, Modbus TCP, CANopen, IEC protocols on request |
Touch-panel HMI with communication
Operator panel (monochrome or colour) that replaces the communication module and frees a slot. Shows real-time values, curves, reports, alarms and operating states of all connected modules, allows parameter changes and includes commissioning and test software.
| Interfaces | 4× RS485, 2× CAN, 1× Ethernet 100 Mbit, 1× USB, wireless optional |
|---|

High-speed acquisition card
FPGA-based card for fast analogue and pulse acquisition with averaging over 1 to 15 000 repetitions, for example for time-of-flight measurement and signal analysis.
| Sampling rate | 100 / 150 / 200 MS/s (12-bit), 300 MS/s (10-bit) |
|---|---|
| Analogue input | ±620 mV, 50 Ω, MCX |
| Pulse in/out | CMOS 3.3 V or LVDS, width ≥ 40 ns |
| Interfaces | Ethernet 100 Mbit, USB 2.0 |
| Power consumption | ≤ 15 W |
Signal converters
Level, isolation and standard-signal converters to connect third-party sensors and legacy equipment to the backplane bus. Configured per project.
Supervisory control systems
Distributed, open systems with supervisory and field level, redundant computers and fibre-optic double ring to the field level. Software of your choice: our own supervisory package or standard packages such as WinCC, iFIX or InTouch.
- Over two hundred installations in power and water facilities
- Unattended or minimally attended operation
- Interfaces to grid dispatch and hydrological systems

Control system for small and medium hydropower plants
Data acquisition, visualisation, schedules and switching logs, event and alarm handling, telecontrol link to the grid dispatch centre. Operating modes: command operation, automatic generation control (AGC), voltage/reactive power control (AVC), economic dispatch, frequency control.
The field level uses a DSP-based unit controller that combines temperature monitoring, generator protection, synchronisation, speed, wicket gate, excitation and governor functions in one device; redundant for machines above 2 MW.
Gate and weir control
For hydraulic, wire-rope and screw drives at power plants, pumping stations and weirs: gate position, water levels and load cells are acquired, the gate moves automatically or manually, locally or remotely. Redundant PLC and power supply, flood schedules, video linkage.
Lock control
For single and multi-stage, single and multi-lane locks: central control with traffic and fee system, field stations for gates and filling valves, public address for skippers, video surveillance. Hardware and software interlocks for safe up- and downstream traffic.
Auxiliary system controls
Cabinets for pressure oil, leakage, low- and high-pressure air, seepage and inspection drainage, fire water, cooling and lubrication oil, high-pressure jacking and cooling fans. Automatic, manual and off modes, main/standby changeover, full motor protection, soft start, fieldbus connection.
Hydropower and lock systems are engineered per project to the regulations applicable at the site (in the EU among others VDE and EN 61508 for safety-related functions).